Abstract | ||
---|---|---|
Instrument current transformers (CTs) can be heavily influenced by DC component in the measured current. 50 A DC current in 500 A CT may cause 40% error in the current and power measurement. For small power factors the situation can be even worse due to 20 deg phase error. We use digital feedback compensation of the DC flux to suppress the overall error to 0.15%. |
Year | DOI | Venue |
---|---|---|
2014 | 10.3390/s16010114 | Sensors (Basel, Switzerland) |
Keywords | DocType | Volume |
current transformers,electric current measurement,error compensation,feedback,instrument transformers,measurement errors,power factor,power measurement,dc component,dc flux,dc-compensated current transformer,current 50 a,current 500 a,current measurement error suppression,digital feedback compensation,instrument current transformer,current transformer,dc tolerance,current sensor,DC tolerance | Conference | 16 |
Issue | ISSN | Citations |
1 | 1424-8220 | 2 |
PageRank | References | Authors |
0.52 | 3 | 3 |
Name | Order | Citations | PageRank |
---|---|---|---|
pavel ripka | 1 | 5 | 2.84 |
Karel Draxler | 2 | 11 | 3.88 |
Renata Styblikova | 3 | 11 | 3.88 |