Title
Metrological Frequency Response Analysis Of A High Current Instrument Transformer
Abstract
This paper presents the metrological frequency response analysis of a high current instrument transformer (HCT) with a rated primary current of 8 kA.A special measuring system is used to identify the frequency response of the HCT at different primary currents in a frequency range up to 40 kHz. The burden dependency of the frequency response is determined by using different resistive and resistive-inductive burdens.The measuring results indicate the good transmission behaviour of the HCT at higher frequencies by applying resistive burdens. However, resonances occur by applying resistive-inductive burdens, resulting in high resonance peaks which deteriorate the transmission behaviour of the HCT and cause high voltages at its secondary side.
Year
DOI
Venue
2015
10.1109/ICSensT.2015.7438476
2015 9TH INTERNATIONAL CONFERENCE ON SENSING TECHNOLOGY (ICST)
Keywords
DocType
ISSN
Instrument transformers, current transformers, frequency response, current measurement
Conference
2156-8065
Citations 
PageRank 
References 
0
0.34
0
Authors
2
Name
Order
Citations
PageRank
Christian Jäschke100.34
Peter Schegner22710.06