Title
Active Filter for the Removal of the DC Current Component for Single-Phase Power Lines.
Abstract
Nonlinear loads and grid-connected converters can cause, in addition to the generation of several current harmonics in the grid current, a dc current component injection. A dc current component can cause the magnetic core saturation of distribution power transformers. Transformers operating under saturation conditions present increased power losses, overheating, and distorted current waveforms. Si...
Year
DOI
Venue
2013
10.1109/TIE.2012.2213562
IEEE Transactions on Industrial Electronics
Keywords
Field
DocType
Inductors,Voltage measurement,Generators,Magnetic cores,Mathematical model,Resistance,Current measurement
Power engineering,Current transformer,Control theory,Volt-ampere,Constant current,Power factor,Electric power system,Control engineering,DC bias,Engineering,Single-phase electric power
Journal