Abstract | ||
---|---|---|
The feedback relay test is usually used to identify one point on the Nyquist diagram of the plant model. It is shown that the derivatives of amplitude and phase of the plant model with respect to frequency at that point can be approximated by the Bode's integrals without any model of the plant. The precision of the approx- imation for typical industrial plant models is studied. The derivatives are used to design a PID controller for slope adjustment of the loop Nyquist diagram and im- prove the closed-loop performance. Simulation exam- ples illustrate the effectiveness and the simplicity of the proposed method to design the PID controllers. |
Year | DOI | Venue |
---|---|---|
2002 | 10.1109/ACC.2002.1025459 | American Control Conference, 2002. Proceedings of the 2002 |
Keywords | DocType | Volume |
Bode diagrams,Nyquist diagrams,closed loop systems,control system synthesis,feedback,integration,three-term control,Bode integrals,Nyquist diagram,PID controller design,closed-loop performance,feedback relay test,industrial plant models,loop Nyquist diagram,slope adjustment | Conference | 6 |